1734-apb profibus adapter – Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 152

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

154 Troubleshoot with the Indicators

1734-APB PROFIBUS Adapter

Indication

Probable Cause

Recommended Action

System Power

Off

Not active - field power is off or DC-DC converter problem. 1. Verify field power is on.

2. Verify backplane power (load current) is not exceeded.
3. Replace 1734-ACNR adapter.

Green

System power is on, and DC-DC converter is active (5V).

None.

Field Power

Off

Not active - field power is off.

Apply power to device.

Green

Power is on - 24V is present.

None.

Adapter
Status

PROFIBUS
Status

PointBus
Status

1734-APB

Field
Power

System
Power

System Power

Field Power

Adapter Status

PROFIBUS Status

POINTBus Status

1734-2

Indication

Probable Cause

Recommended Action

Adapter Status

Off

No power supplied.

Hardware check is in progress.

Initialization is in progress.

1. Apply power.

2. Wait for power self-test to complete.

Green

Operation is normal.

None.

Red

Hardware check fault present.

Replace device.

Indication

Probable Cause

Recommended Action

PROFIBUS Status

Off

No power supplied.
Bus is offline.

Apply power, verify network cabling, and correct, as needed.

Solid green

Bus is online (data exchange).

None.

Flashing green

Adapter received a CLEAR command from the master.

None.

Solid red

Error in PROFIBUS initialization is present.
No modules installed in the backplane.

Verify configuration, proper installation of modules, and
correct, as needed.