12 Install POINT I/O Modules

2. Make certain the DIN-rail locking screw is in the horizontal position,

noting that you cannot insert the module if the locking mechanism is
unlocked.

3. Insert the module straight down into the mounting base and press to

secure, locking the module into place.

Install the Removable
Terminal Block

A removable terminal block is supplied with your mounting base assembly. To
remove, pull up on the removable terminal block (RTB) handle. This lets you
remove and replace the base as necessary without removing any of the wiring. To
reinsert the removable terminal block, proceed as follows.

1. Insert the RTB end opposite the handle into the base unit.

This end has a curved section that engages with the mounting base.

46149

24V

DC

So

urce
Outp

ut

Mo

dule

Sta

tus

Netw

ork

Sta

tus

17

34
OB4E

NODE:

0

1

2

3

46150

WARNING: When you connect or disconnect the RTB with field-side
power applied, an electrical arc can occur. This could cause an explosion
in hazardous location installations. Be sure to remove power or that the
area is nonhazardous before proceeding.