Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

Default Data Maps 167

Produce 1 (Rx)

SC 3

SC 2

SC 1

SC 0

OW 3

OW 2

OW 1

OW 0

Consume (Tx)

No consumed data

Where: OW = open wire, SC = short circuit, fault = open wire or short circuit.

Data Map - Produced Assembly Instance 23

Message Size: 1 Byte

7

6

5

4

3

2

1

0

Produce 0 (Rx)

Fault 3

Fault 2

Fault 1

Fault 0

Input 3

Input 2

Input 1

Input 0

Consume (Tx)

No consumed data

Where: Fault = open wire or short circuit.

Default Data Map - Configuration Assembly Instance 103

Message Size: 18 Bytes

7

6

5

4

3

2

1

0

Consume 0

Input 0 Off to On Filter Byte 0

Consume 1

Input 0 Off to On Filter Byte 1

Consume 2

Input 0 On to Off Filter Byte 0

Consume 3

Input 0 On to Off Filter Byte 1

Consume 4

Input 1 Off to On Filter Byte 0

Consume 5

Input 1 Off to On Filter Byte 1

Consume 6

Input 1 On to Off Filter Byte 0

Consume 7

Input 1 On to Off Filter Byte 1

Consume 8

Input 2 Off to On Filter Byte 0

Consume 9

Input 2 Off to On Filter Byte 1

Consume 10

Input 2 On to Off Filter Byte 0

Consume 11

Input 2 On to Off Filter Byte 1

Consume 12

Input 3 Off to On Filter Byte 0

Consume 13

Input 3 Off to On Filter Byte 1

Consume 14

Input 3 On to Off Filter Byte 0

Consume 15

Input 3 On to Off Filter Byte 1

Consume 16

Autobaud Disable

Enable OW3

Enable OW2

Enable OW1

Enable OW0

Consume 17

Produced Assembly Instance

Produce (Tx)

No produced data

Where: OW = open wire.

Default Data Map - Produced Assembly Instance 101

Message Size: 2 Bytes