156 Troubleshoot with the Indicators

1734-AENT EtherNet/IP Adapter

System Power

Field Power

43248

Module Status

Network Activity

Network Status
POINTBus Status

Module
Status

Network
Activity

Network
Status

1734-AENT

PointBus
Status

Field
Power

System
Power

0 2

0

Indication

Probable Cause

Recommended Action

Module Status

Off

No power applied to device

Apply power to the device.

Flashing red/green

LED power cycle test (module self-test) present.

None.

Solid green

Device is operating normally.

None.

Flashing red

Recoverable fault has occurred.

Firmware (NVS) update present.

Address switches changed.

1. Complete firmware update.
2. Verify address switches.

Solid red

Unrecoverable fault has occurred.

Self-test failure present (checksum failure, or ramtest failure at power cycle).

Firmware fatal error present.

Replace adapter.

Indication

Probable Cause

Recommended Action

POINTBus Status

Off

Device not powered - check module status indicator.

Apply power to device.

Flashing red/green

LED power cycle test present.

None.

Flashing red

Recoverable fault occurred:

At power cycle the number of expected modules does not equal

the number of modules present

A module is missing

Node fault (I/O connection timeout) occurred.

Configure chassis size.

Check for missing module and reinstall as needed.

Check for I/O module failure and correct as needed.

Solid red

Unrecoverable fault occurred - the adapter is bus off.

1. Cycle power to device.
2. If condition persists, replace device.

Flashing green

Firmware (NVS) update in progress.

None.

Solid green

Adapter online with connections established (normal operation,
Run mode).

None.