1734-pdn devicenet communication interface module, Troubleshoot i/o communication modules – Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 147

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

Troubleshoot with the Indicators 149

Troubleshoot I/O
Communication Modules

The status indicators on the communication modules provide system power and
DeviceNet power indications.

1734-PDN DeviceNet Communication Interface Module

System Power

DeviceNet Power

Indicator

Indication

Probable Cause

Recommended Action

System Power

Off

Device is not active.

DeviceNet power is off, or DC-

DC converter problem is
present.

1. Verify DeviceNet power is on, and apply power if needed.
2. Verify backplane power not exceeded, and correct, as needed.
3. Replace 1734-PDN module.

Green

System power is on.

DC-DC converter is active (5V).

None.

DeviceNet Power

Off

Device is not active.

DeviceNet power is off.

Apply DeviceNet 24V power.

Green

Power is on with 24V present.

None.