Devicenet connector wiring – Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 81

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

Install POINTBlock I/O Modules 83

Output Wiring Diagram

(Load Powered by External Power)

DeviceNet Connector Wiring

Channel

Output

Common

Supply

Remote Termination Block 3

0A

0

Not used

Not used

0B

2

1A

1

1B

3

2A

4

2B

6

3A

5

3B

7

Remote Termination Block 4

4A

0

Not used

Not used

4B

2

5A

1

5B

3

6A

4

6B

6

7A

5

7B

7

Supply voltage can range from +5V DC to 240V ac, depending on relay load.
12/24V DC power for the module is provided by the internal power bus.

ATTENTION: When connecting more than one wire in a
termination point, make sure that both wires are the same gauge
and type.

Out
0A

Out
0B

Out
1A

Out
1B

Load

Power
Supply

Out = Output channel relay contacts
Power Supply = can range from +5V DC to 240V ac
C = Common

0

2

4

6

3

5

7

1

Power
Supply

Load

Out
2A

Out
2B

Out
3A

Out
3B

DeviceNet
Connection

Red

White

Bare

Blue
Black

-V

+V

CAN - High

Shield

CAN - Low

Advertising