Devicenet connector wiring – Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual
Page 81

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
Install POINTBlock I/O Modules 83
Output Wiring Diagram
(Load Powered by External Power)
DeviceNet Connector Wiring
Channel
Output
Common
Supply
Remote Termination Block 3
0A
0
Not used
Not used
0B
2
1A
1
1B
3
2A
4
2B
6
3A
5
3B
7
Remote Termination Block 4
4A
0
Not used
Not used
4B
2
5A
1
5B
3
6A
4
6B
6
7A
5
7B
7
Supply voltage can range from +5V DC to 240V ac, depending on relay load.
12/24V DC power for the module is provided by the internal power bus.
ATTENTION: When connecting more than one wire in a
termination point, make sure that both wires are the same gauge
and type.
Out
0A
Out
0B
Out
1A
Out
1B
Load
Power
Supply
Out = Output channel relay contacts
Power Supply = can range from +5V DC to 240V ac
C = Common
0
2
4
6
3
5
7
1
Power
Supply
Load
Out
2A
Out
2B
Out
3A
Out
3B
DeviceNet
Connection
Red
White
Bare
Blue
Black
-V
+V
CAN - High
Shield
CAN - Low