1734-ox2 2-relay output modules – Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 48

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

32 Install POINT I/O Modules

1734-OX2 2-relay Output Modules

1734-OX2 Module with Load Powered by Internal Power Bus
Wiring Diagram

ATTENTION: Relay contacts are not powered by the internal power bus.
Load power can be provided by the internal power bus or an external
power source.

Channel

Output

Relay Common

Supply

0 (N.C.)

0

4

6

0 (N.O.)

2

1 (N.C.)

1

5

7

1 (N.O.)

3

Supply voltage can range from +5V DC…240V AC, depending on relay load.
12V, 24V DC, 120V, 240V AC power for the module is provided by the internal power bus.

Relay

Output

Module

Status

Network

Status

1734

OX2

NODE:

0

1

0

1

2

3

4

5

6

7

41974

Module Status

Network Status

Status of Output 0

Status of Output 1

Output 0 Relay Common - RC

+V

RC - Output 1 Relay Common

+V

Output 0 Connection - NC

Output 0 Connection - NO

NC - Output 1 Connection

NO - Output 1 Connection

NC = Normally closed
NO = Normally open
RC = Relay Common
+V = Positive Supply

+V

+V

Out 0
NC

Out 1
NC

Load

Load

0

2

4

6

3

5

7

1

L1

L1

NC = Normally closed
NO = Normally open
RC = Relay Common
+V = Positive Supply

L2/N

L2/N

Out 0
NO

Out 1
NO

Out 0
RC

Out 1
RC

Advertising