Calibrate the analog current input module, Important, Aent ie2c ethernet/ip input – Rockwell Automation 1734-XXXX POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual

Page 119: Current source power supply voltage

Advertising
background image

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013

Calibrate Your Analog Modules 121

Calibrate the Analog
Current Input Module

To calibrate your current input module, connect the module in a system similar
to that shown in the figure.

1. Double-click the icon to bring up the General parameter dialog.

IMPORTANT

Apply power to the power supply and module for at least
10 minutes before calibrating the module. This allows
internal temperatures to stabilize, and reduces drift errors.

0

1

0

1

0

1

0

1

0

1

0

1

PDN IE2C

250

Ω

Current Source

DeviceNet Input

Power Supply Voltage

Channel 0
Connect to 0 and 4

Channel 1
Connect to 1 and 5

250

Ω

resistor

protects the current
source in the event
of shorted wires.

0

1

0

1

0

1

0

1

0

1

0

1

0

1

Module
Status

Network Activity
Status

Network
Status

1734-AENT

PointBus
Status

Field
Power

System
Power

0 2

0

AENT IE2C

EtherNet/IP Input

44037

Current Source

Power Supply Voltage

250

Ω

Channel 0
Connect to 0 and 4

Channel 1
Connect to 1 and 5

250

Ω

resistor

protects the current
source in the event
of shorted wires.

44035

Advertising