126 Calibrate Your Analog Modules

2. From the EDS editor dialog, click Upload.

3. Click Device Parameters.

You see the Device Parameters dialog.

4. Select Calibration at the Group pull-down.

5. From the Device Parameters dialog, click Calibration Command, and

select Begin Calibration.

6. From the Device Parameters dialog, click the Download to Device button.