Network and Module Status Indications

The network and module status indications are the same for all modules.

Module Status

Network Status

24VDC

Sink

Input

Module

Status

Network

Status

1734

IB2

NODE:

0

1

Indication

Probable Cause

Recommended Action

Module Status

Off

No power applied to device.

Apply power to device.

Solid green

Device is operating normally.

None.

Flashing green

Device needs commissioning due to configuration missing,
incomplete, or incorrect.

Configure device properly.

Flashing red

Recoverable fault is present.
Device did not pass internal test.

1. Cycle power to device.
2. If condition persists, replace device.

Solid red

Unrecoverable fault may require device replacement.

Replace device.

Flashing red/green

Device is in self-test.

None.

Network Status

Off

Device is not online.
- Device has not completed Auto Baud detection
because there is no network traffic.
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator.

Apply power to device, wait for MAC_id to complete, and
correct, as needed.

Flashing green

Device is online but has no connections in the established
state.

None - device is in Idle or Program mode.

Solid green

Device is online and has connections in the established state.

None.

Flashing red

One or more I/O connections are in timed-out state.

Check for I/O module failure, and correct, as needed.

Solid red

Critical link failure is present with failed communication device.
Device detected error that prevents it from communicating on
the network.

Verify that adapter and terminal bases are properly installed,
and reinstall, as needed.

Flashing red/green

Communication faulted device - the device has detected a
network access error and is in communication faulted state.
Device has received and accepted an Identify Communication
Faulted Request - long protocol message.

Verify that adapter is properly installed, and reinstall, as
needed.