Communication with serial devices – Rockwell Automation 1756-L6x_L7x ControlLogix System User Manual User Manual

Page 103

Advertising
background image

Rockwell Automation Publication 1756-UM001O-EN-P - October 2014

103

Serial Communication on 1756-L6x Controllers

Chapter 6

Communication with
Serial Devices

When configuring the controller for serial communication, you first specify a
Serial Port mode (System or User), then a protocol.

Figure 18 - Serial Port Mode in the Controller Properties

Table 23

describes the serial communication protocols for use with each mode.

Table 23 - Serial Port Modes, Protocols, and Uses

Mode

Protocol

Is used to

See page

System

DF1 Master

Control polling and message transmission between the master and slave nodes.

104

DF1 Point to Point

Communicate between the controller and one other DF1-protocol-compatible device.
Program the controller via the serial port.

105

DF1 Radio Modem

Communication with SLC 500 and MicroLogix™ 1500 controllers.
This protocol supports master/slave and store/forward configurations.

106

DF1 Slave

Configure the controller as a slave station in a master/slave serial communication network.

109

DH-485

Communication with other DH-485 devices via a multi-master and token-passing network that enables
programming and peer-to-peer messaging.

110

User

ASCII

Communicate with ASCII devices.
Use ASCII instructions to read and write data from and to an ASCII device.

112

Advertising