Foundation fieldbus communication – Rockwell Automation 1756-L6x_L7x ControlLogix System User Manual User Manual

Page 98

Advertising
background image

98

Rockwell Automation Publication 1756-UM001O-EN-P - October 2014

Chapter 5

Communication Networks

1.

Configure the remote I/O adapter.

2.

Lay out the remote I/O network cable.

3.

Connect the remote I/O network cable.

4.

Configure the scanner channel.

For more information to configure a remote I/O network with the 1756-RIO,
1756-DHRIO, or 1756-DHRIOXT modules, see these publications:

Data Highway Plus-Remote I/O Communication Interface Module User
Manual, publication

1756-UM514

ControlLogix Remote I/O Communication Module User Manual,
publication

1756-UM534

As you design your remote I/O network, remember the following:

All devices that are connected to a remote I/O network must
communicate by using the same communication rate. These rates are
available for remote I/O:

57.6 Kbps

115.2 Kbps

230.4 Kbps

You must assign unique partial and full racks to each channel used in
Remote I/O Scanner mode.

Both channels of a 1756-DHRIO or 1756-DHRIOXT module cannot
scan the same partial or full rack address. Both module channels can
communicate to 00…37 octal or 40…77 octal, but each channel can
communicate only with one address at a time in whichever of these two
ranges it falls.

Foundation Fieldbus
Communication

Foundation Fieldbus is an open interoperable fieldbus that is designed for process
control instrumentation. The fieldbus devices that are described in

Table 22

can

be connected to the ControlLogix controller via another network as shown in
the following example.

Table 22 - Fieldbus Devices and Capabilities

Fieldbus Device

Is used to

1788-EN2FFR

Bridge an EtherNet/IP network to Foundation Fieldbus.
Connect via a low-speed serial (H1) and high-speed Ethernet (HSE) network

connections.

Access devices directly via an OPC server.

1788-CN2FFR

Connect via low-speed serial (H1) connections.
Bridge a ControlNet network to a Foundation Fieldbus.
Support redundant ControlNet media.

Advertising