Estimate the esm support of the wallclocktime, Maintain the battery (only 1756-l6x controllers), Check the battery status – Rockwell Automation 1756-L6x_L7x ControlLogix System User Manual User Manual

Page 72: And st

Advertising
background image

72

Rockwell Automation Publication 1756-UM001O-EN-P - October 2014

Chapter 3

Start Using the Controller

Estimate the ESM Support
of the WallClockTime

The ESM provides support for the maintenance of the WallClockTime of the
controller when power is not applied. Use this table to estimate the hold-up time
of the ESM based on the temperature of the controller and installed ESM.

To check the status of the ESM, see

General Status Messages on page 186

.

Maintain the Battery (Only
1756-L6x
Controllers)

This section explains how to monitor and maintain the lithium batteries that the
ControlLogix controllers support.

For further information, see the

Additional Resources

section in the preface.

Check the Battery Status

When the battery is approximately 95% discharged, these low-battery warnings
are indicated:

The BAT is solid red.

A minor fault (type 10, code 10) is logged.

Hold-up Time (in days)

Temperature

1756-ESMCAP

1756-ESMNRM

1756-ESMNSE

20

°

C (68

°

F)

12

12

0

40 °C (104

°

F)

10

10

0

60

°

C (140

°

F)

7

7

0

IMPORTANT

Any action that causes the 1756-L7x controller to reset (hard or soft), without
an ESM installed, results in the controller’s wal clock time of the controller
being reset to the factory default of 01/01/1998.

Table 6 - 1756-L6x Controllers and Compatible Batteries

Cat. No.

Series

Compatible Battery

1756-L61
1756-L62
1756-L63

A

1756-BA1
or
1756-BATA
or
1756-BATM

1756-L61
1756-L62
1756-L63
1756-L64
1756-L65

B

1756-BA2

1756-L63XT

B