Rockwell Automation 1756-L6x_L7x ControlLogix System User Manual User Manual
Page 116

116
Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Chapter 6
Serial Communication on 1756-L6x Controllers
Use this table when specifying settings for the protocols listed.
Field
DF-1 Master Protocol
DF-1 Slave Protocol
DF-1 Radio Modem Protocol
Station Address
Controller station address number
Controller station address number
Controller station address number
Transmit Retries
3
3
N/A
ACK Timeout
50
N/A
N/A
Slave Poll Timeout
N/A
3000
N/A
Reply Message Wait
5
N/A
N/A
Polling Mode
Message: polls the slave by using the Message
instruction
Slave: initiates messages for slave-to-slave
broadcast
Standard: schedules polling for the slave
N/A
N/A
EOT Suppression
N/A
Disable
N/A
Error Detection
BCC
BCC
BCC
Duplicate Detection
Enabled
Enabled
N/A
Enable Store and Forward
N/A
N/A
Choose enable if you want to use the store
and forward tag.
The last bit of the INT[16] Enable Store and
Forward array must be ’enabled.’ For
example, say that you create an INT[16] tag
named EnableSandF. Then
EnableSandF[15].15 must be set to 1 for
broadcast to work on radio modem.