Use this table when specifying settings for the protocols listed.

Field

DF-1 Master Protocol

DF-1 Slave Protocol

DF-1 Radio Modem Protocol

Station Address

Controller station address number

Controller station address number

Controller station address number

Transmit Retries

3

3

N/A

ACK Timeout

50

N/A

N/A

Slave Poll Timeout

N/A

3000

N/A

Reply Message Wait

5

N/A

N/A

Polling Mode

Message: polls the slave by using the Message
instruction
Slave: initiates messages for slave-to-slave
broadcast
Standard: schedules polling for the slave

N/A

N/A

EOT Suppression

N/A

Disable

N/A

Error Detection

BCC

BCC

BCC

Duplicate Detection

Enabled

Enabled

N/A

Enable Store and Forward

N/A

N/A

Choose enable if you want to use the store
and forward tag.
The last bit of the INT[16] Enable Store and
Forward array must be ’enabled.’ For
example, say that you create an INT[16] tag
named EnableSandF. Then
EnableSandF[15].15 must be set to 1 for
broadcast to work on radio modem.

Advertising