Rockwell Automation Publication 1756-UM001O-EN-P - October 2014

Chapter 3

Start Using the Controller

Estimate 1756-BA2 Battery Life After Warnings

Use this table to estimate the battery life after the low-battery warnings are
indicated. Use these times even if the controller does not have power because
there is a small power-drain on the battery.

IMPORTANT

When you power up the controller, see if there is a low-battery warning. If
you get a low-battery warning for the first time, you have less battery life
than this table shows. While powered down, the controller still drains the
battery but it cannot give the low-battery warning.

Temperature 2.54 cm (1 in.)
Below the Chassis, max

Power Cycles

Battery Life After the BAT Status Indicator Turns Red (worst case)

Project Size

1 MB

2 MB

4 MB

8 MB

16 MB

0…20 °C (32…68 °F)

3 per day

26 weeks

18 weeks

12 weeks

9 weeks

5 weeks

1 per day

26 weeks

26 weeks

26 weeks

22 weeks

13 weeks

1 per month

26 weeks

26 weeks

26 weeks

26 weeks

26 weeks

21…40 °C (69.8…104 °F)

3 per day

18 weeks

14 weeks

10 weeks

8 weeks

5 weeks

1 per day

24 weeks

21 weeks

18 weeks

16 weeks

11 weeks

1 per month

26 weeks

26 weeks

26 weeks

26 weeks

26 weeks

41…45 °C (105.8…113 °F)

3 per day

12 weeks

10 weeks

7 weeks

6 weeks

4 weeks

1 per day

15 weeks

14 weeks

12 weeks

11 weeks

8 weeks

1 per month

17 weeks

17 weeks

17 weeks

17 weeks

16 weeks

46…50 °C (105.8…113 °F)

3 per day

10 weeks

8 weeks

6 weeks

6 weeks

3 weeks

1 per day

12 weeks

11 weeks

10 weeks

9 weeks

7 weeks

1 per month

12 weeks

12 weeks

12 weeks

12 weeks

12 weeks

51…55 °C (123.8…131 °F)

3 per day

7 weeks

6 weeks

5 weeks

4 weeks

3 weeks

1 per day

8 weeks

8 weeks

7 weeks

7 weeks

5 weeks

1 per month

8 weeks

8 weeks

8 weeks

8 weeks

8 weeks

56…60 °C (132.8…140 °F)

3 per day

5 weeks

5 weeks

4 weeks

4 weeks

2 weeks

1 per day

6 weeks

6 weeks

5 weeks

5 weeks

4 weeks

1 per month

6 weeks

6 weeks

6 weeks

6 weeks

6 weeks

EXAMPLE

Under these conditions, the battery lasts at least 20 months before the BAT
status indicator turns red:

The maximum temperature 2.54 cm (1 in.) below the

chassis = 45 °C (113 °F).

You cycle power to the controller three times per day.

The controller contains an 8 MB project.