Online Additions - ControlNet Considerations

ControlNet considerations that must be made depend upon the ControlLogix
ControlNet modules you are using.

1756-CNB and 1756-CNBR Modules

When you add I/O to the ControlNet network via the 1756-CNB or
1756-CNBR modules while online, these considerations must be made:

Digital I/O modules can be added as rack-optimized connections if the
parent module is configured with rack-optimized connections.

Digital I/O modules can also be added as direct connections.

Analog I/O modules can be added only as direct connections.

Disable the Change of State (COS) feature on digital input modules
because it can cause inputs to be sent more quickly than the RPI.

If you plan to add large amounts of I/O to the ControlNet network,
dedicate one ControlNet network for I/O. For the dedicated
ControlNet network, verify that there is little or none of the following:

HMI traffic

MSG traffic

Programming workstations

IMPORTANT

These ControlLogix modules cannot be added while online:

Motion modules (1756-MO2AE, 1756-HYD02, 1756-MO2AS, 1756-MO3SE,

1756-MO8SE, 1756-MO8SEG, 1756-M16SE)

1756-RIO

1756-SYNCH

1756-56AMXN

TIP

While you can add a new digital I/O module to an existing rack-optimized
connection, you cannot add rack-optimized connections while online.