Rockwell Automation Publication 1756-UM001O-EN-P - October 2014

49

Start Using the Controller

Chapter 3

Connect to the
1756-L6x
Controller

The 1756-L6

x ControlLogix controller uses a serial port for workstation

connections.

To connect a workstation to the serial port, you can make your own serial cable or
use one of these cables:

1756-CP3 serial cable

1747-CP3 cable from the SLC™ product family (if you use this cable, it can
be difficult to close the controller door)

Follow these guidelines if you make your own serial cable:

Limit the length to 15.2 m (50 ft).

Wire the connectors as shown.

Attach the shield to the connectors.

Plug the controller end of the serial cable into the RS-232 port on the front of the
controller.

WARNING: If you connect or disconnect the serial cable with power applied to
this module or the serial device on the other end of the cable, an electrical arc
can occur. This could cause an explosion in hazardous location installations.

Be sure that power is removed or the area is nonhazardous before proceeding.

To Workstation

To Controller

2 RDX

3 TXD

4 DTR

COMMON

6 DSR

7 RTS

8 CTS

9

1 CD

2 RDX

3 TXD

4 DTR

COMMON

6 DSR

7 RTS

8 CTS

9

1 CD

To Workstation

To Controller