If the module has a Real Time Sample (RTS), disable it or set it to a rate
that is greater than the RPI.

You can add I/O modules until you reach these limits:

80% of CPU utilization of the 1756-CN2, 1756-CN2R, or
1756-CN2RXT communication module.

Less than 400,000 unscheduled bytes per second are displayed in
RSNetWorx for ControlNet software after the network has been
scheduled.

Online Additions—EtherNet/IP Considerations

When you add I/O modules to the EtherNet/IP network, make these
considerations:

The EtherNet/IP I/O modules that you add can be added as these
connection types:

Rack-optimized connections, including new and existing connections

Direct connections

You can add I/O modules until you reach the limits of the communication
connections of the module.

For EtherNet/IP module limitations, see the EtherNet/IP Modules in
Logix5000 Control Systems User Manual, publication

ENET-UM001

.

Determine When Data is
Updated

ControlLogix controllers update date asynchronously with the execution of logic.
Use this flowchart to determine when a producer, such as a controller, input
module, or bridge, sends data.