Redundant Systems

ControlLogix Redundancy
Overview

Redundancy provides more system availability by switching control to a
secondary controller chassis if a fault occurs in the primary controller chassis.

The redundant system switches control from the primary to the secondary when
these faults occur:

Power loss to primary chassis

Hardware or firmware failure of any module in the primary chassis

A major fault in the user program on the primary controller

Loss of communication between the primary chassis and remote
ControlNet or EtherNet/IP modules

Disconnection of an Ethernet patch cable from an EtherNet/IP
communication module in the primary chassis

Removal or insertion of any module in the primary chassis

A user command that causes a switchover

Topic

Page

ControlLogix Redundancy Overview

175

System Requirements

177

System Considerations

178

Build a Redundant System

179

ControlNet Considerations in Redundant Systems

180

EtherNet/IP Considerations in Redundant Systems

180

Redundancy and Scan Time

181