Appendix A

Troubleshoot the Module

OK Indicator

The OK indicator shows the state of the controller.

1756-L6x Status Indicators

The 1756-L6

x controllers have status indicators on the front of the controller

that show the state of the controller.

RUN Indicator

Use the mode switch on the front of the controller or use the Controller Status
menu in the Logix Designer application to change the controller mode that is
shown by the RUN indicator.

Table 55 - OK Indicator

State

Description

Off

No power is applied to the controller.

Flashing red

Either of the following is true:
It is a new controller, out of the box, and it requires a firmware upgrade. If a firmware

upgrade is required, the status display indicates Firmware Installation Required. To upgrade
firmware, see

Upgrade Controller Firmware on page 52

.

It is a previously used or in-use controller and a major fault has occurred. For details about

major recoverable and nonrecoverable faults, see the Logix5000 Major, Minor, and I/O Fault
Codes Programming Manual, publication

1756-PM014

.

Solid red

One of the following is true:
The controller is completing power-up diagnostics.
The charge of the capacitor in the ESM is being discharged upon powerdown.
The controller is powered, but is inoperable.
The controller is loading a project to nonvolatile memory.

Solid green

The controller is operating normally.

Table 56 - RUN Indicator

State

Description

Off

The controller is in Program or Test mode.

Steady green

The controller is in Run mode.

Status Indicators