Chapter 6

Serial Communication on 1756-L6x Controllers

DH-485 Protocol

The controller can send and receive messages to and from other controllers on a
DH-485 network. The DH-485 connection supports remote programming and
monitoring via the Logix Designer application. However, excessive traffic over a
DH-485 connection can adversely affect overall controller performance and lead
to timeouts and decreased performance of the configuration.

You can also use a 1756-DH485 module to connect the ControlLogix chassis to a
DH-485 network with multiple controllers. For more information, see the
ControlLogix DH-485 Communication Module User Manual, publication

1756-UM532

.

The DH-485 protocol uses RS-485 half-duplex as its physical interface. RS-485
is a definition of electrical characteristics, not a protocol. You can configure the
RS-232 port of the ControlLogix controller to act as a DH-485 interface.

To connect the controller to the DH-485 network, you must use these
components:

A 1761-NET-AIC converter (two controllers can be connected to one
converter)

An RS-232 cable (catalog number 1756-CP3 or 1747-CP3) for each
controller to connect to the converter

IMPORTANT

Use Logix5000 controllers on DH-485 networks only when you want to add
controllers to an existing DH-485 network.

For new applications with Logix5000 controllers, we recommend that you
use networks in the NetLinx open architecture.