1756-ba1 or 1756-bata battery life – Rockwell Automation 1756-L6x_L7x ControlLogix System User Manual User Manual

Page 73

Advertising
background image

Rockwell Automation Publication 1756-UM001O-EN-P - October 2014

73

Start Using the Controller

Chapter 3

1756-BA1 or 1756-BATA Battery Life

To estimate how long a 1756-BA1 or 1756-BATA battery can support controller
memory on 1756-L6

x, series A controllers, perform this procedure.

1.

Determine the temperature 2.54 cm (1 in.) below the chassis.

2.

Determine the weekly percentage of time that the controller is turned on.

3.

Determine the estimated worst-case battery life before and after the BAT
status indicator turns on.

4.

For each year of battery life, decrease the time before the BAT status
indicator turns on by the percentage that is shown in the table.

Do not decrease the time after the BAT status indicator turns on.

IMPORTANT: To prevent possible battery leakage, even if the BAT status
indicator is off, replace a battery according to this schedule.

EXAMPLE

If a controller is Off at one of these times:

8 hr/day during a 5-day work week

All day Saturday and Sunday

Then the controller is off 52% of the time:

Total hours per week = 7 x 24 = 168 hrs

Total off hours per week = (5 days x 8 hr/day) + Saturday +

Sunday = 88 hrs

Percentage off time = 88/168 = 52%

IMPORTANT

If the BAT status indicator turns on when you apply power to the
controller, the remaining battery life can be less than

Table 7

indicates.

Some of the battery life can be used up while the controller is off and
unable to turn on the BAT status indicator.

If the temperature 2.54 cm (1 in.)
below the chassis is

Replace the battery within

-25…35

°C (-13…95 °F)

No replacement required

36…40

°C (96.8…104 °F)

3 years

41…45

°C (105.8…113 °F)

2 years

46…50

°C (114.8…122 °F)

16 months

51…55

°C (123.8…131 °F)

11 months

56…70

°C (132.8…158 °F)

8 months

Advertising