Manually change states – Rockwell Automation 1756-L6x_L7x ControlLogix System User Manual User Manual

Page 173

Advertising
background image

Rockwell Automation Publication 1756-UM001O-EN-P - October 2014

173

Using the PhaseManager Tool

Chapter 11

Manually Change States

You can manually change an equipment phase. To change a PhaseManager state,
perform this procedure.

1.

Open the Equipment Phase Monitor.

2.

Take ownership of the equipment phase by clicking Owners and clicking
Yes.

3.

Click the command that initiates the state you need (for example, Start or
Reset).

4.

After you have finished manually changing the state, click Owners to
release your ownership.

Table 43 - PhaseManager Transitions

Type of Transition

Description

Command

A command tells the equipment to do something. For example, the operator pushes the start
button to begin production and the stop button to halt production.
The PhaseManager tool uses these commands:

Reset

Stop

Restart

Start

Hold

Abort

Done

Equipment goes to a waiting state when it is finished with what it is doing. You do not give the
equipment a command. Instead, you configure your code to signal when the phase state is
finished.

Fault

A fault tells you that something out of the ordinary has happened. You configure your code to
look for faults and act if it finds any. If you want to shut down your equipment as quickly as
possible when it detects a fault, configure your code to look for that fault and give the abort
command if it finds it.

Advertising