Troubleshoot the Module

1756-L7x Controller Status
Display and Indicators

The 1756-L7

x controllers have four status indicators and one four-character

scrolling status display.

Figure 47 - 1756-L7x Status Display and Indicators

1756-L7x Controller
Status Display

The 1756-L7

x controller status display scrolls messages that provide information

about the firmware revision, ESM status, project status, and major faults of the
controller.

General Status Messages

The messages that are described in

Table 48

are typically indicated upon

powerup, powerdown, and while the controller is running to show the status of
the controller and the ESM.

Scrolling Status Display, see

page 186

Status Indicators, see

page 195

Table 48 - General Status Messages

Message

Interpretation

No message is indicated

The controller is Off.
Check the OK indicator to determine if the controller is powered and determine the state of the controller.

TEST

The controller is conducting power-up tests.

PASS

Power-up tests have been successfully completed.

SAVE

A project is being saved to the SD card. You can also view the

SD Indicator

(see

page 195

) for more status information.

Allow the save to complete before:
removing the SD card.
disconnecting power.

LOAD

A project is being loaded from the SD card at controller powerup. You can also view the

SD Indicator

(see

page 195

) for more status information.

Allow the load to complete before doing the following:
Removing the SD card
Disconnecting power
Removing the ESM module

UPDT

A firmware upgrade is being conducted from the SD card upon powerup. You can also view the

SD Indicator

(see

page 195

) for more status information.

If you do not want the firmware to update upon powerup, change the Load Image property of the controller.

CHRG