Rockwell Automation Publication 1756-UM001O-EN-P - October 2014

55

Start Using the Controller

Chapter 3

7.

Click Finish.

8.

When a confirmation dialog box appears, click Yes.

The progress dialog box indicates the progress of the firmware upgrade.
1756-L7

x controllers indicate progress in updates and blocks. 1756-L6x

controllers indicate progress only in blocks.

When the upgrade is complete, the Update Status dialog box indicates that
the upgrade is complete.

TIP

If you are using a 1756-L7x controller and experience a Script File Error after selecting the firmware revision number (see the
following example), there is likely an anomaly with your firmware files.

To recover, perform the following:

Go to

http://www.rockwellautomation.com/support/

and download the firmware revision you are trying to upgrade.

Replace the firmware revision that you have previously installed with that posted on the Technical Support website.

If the replacement firmware revision does not resolve the anomaly, contact Rockwell Automation Technical Support.

1756-L6x Controller Progress

1756-L7x Controller Progress

WARNING: Allow the firmware update to fully complete before cycling power
or otherwise interrupting the upgrade.

TIP

If the ControlFLASH upgrade of the controller is interrupted, the 1756-L6x and
1756-L7x controllers revert to boot firmware, that is firmware revision 1.xxx.