140

Rockwell Automation Publication 1756-UM001O-EN-P - October 2014

Chapter 8

I/O Modules

Because of the increased performance that is provided by the 1756-CN2,
1756-CN2R, and 1756-CN2RXT modules, many of the considerations that
must be made with the 1756-CNB and 1756-CNBR modules are not applicable.
With the 1756-CN2, 1756-CN2R, and 1756-CN2RXT modules, you can add
I/O while online as long as you use reasonable RPI settings and remain within
the CPU limitations of the ControlNet module.

When adding to the I/O Configuration with 1756-CN2, 1756-CN2R, and
1756-CN2RXT modules, make these considerations:

Digital I/O modules can be added as rack-optimized connections if the
parent module is configured with rack-optimized connections.

Digital I/O modules can also be added as direct connections.

Analog I/O modules can be added only as direct connections.

Disable the Change of State (COS) feature on digital input modules
because it can cause inputs to be sent more quickly than the RPI.

If you plan to add large amounts of I/O to the ControlNet network,
dedicate one ControlNet network for I/O. For the dedicated ControlNet
network, verify that there is little or none of the following:

HMI traffic

MSG traffic

Programming workstations

9

15.00%

3.3

13.20%

4.0

7.00%

10.0

4.80%

20.0

3.20%

50.0

2.60%

100.0

10

15.60%

3.6

13.20%

4.0

7.50%

10.0

5.20%

20.0

3.40%

50.0

2.70%

100.0

11

16.40%

3.8

13.50%

4.0

8.20%

10.0

5.50%

20.0

3.50%

50.0

2.70%

100.0

12

17.00%

3.8

14.00%

4.0

8.80%

10.0

5.80%

20.0

3.70%

50.0

2.80%

100.0

13

17.80%

3.7

14.60%

4.0

9.30%

10.0

6.10%

20.0

3.80%

50.0

2.90%

100.0

14

18.50%

3.7

15.20%

4.0

9.90%

10.0

6.40%

20.0

4.00%

50.0

2.90%

100.0

15

19.40%

3.9

15.80%

4.0

10.50%

10.0

6.70%

20.0

4.10%

50.0

3.00%

100.0

(1) Example assumes that adequate unscheduled bandwidth is available.
(2) Approximate use of the central-processing unit (CPU) of the module in percent.
(3) The average Actual Packet Interval with 2000 samples (shown in ms).

Table 35 - 1756-CN2, 1756-CN2R, and 1756-CN2RXT Performance Example

(1)

No. of Direct
Analog I/O
Connections
Added Online

RPI = 2 ms

RPI = 4 ms

RPI = 10 ms

RPI = 20 ms

RPI = 50 ms

RPI = 100 ms

CPU %

(2)

Avg.
API

(3)

CPU %

(2)

Avg.
API

(3)

CPU %

(2)

Avg.
API

(3)

CPU %

(2)

Avg.
API

(3)

CPU %

(2)

Avg.
API

(3)

CPU %

(2)

Avg.
API

(3)

TIP

While you can add a new digital I/O module to an existing rack-
optimized connection, you cannot add rack-optimized connections
while online.