1756-l7x controller status indicators, Run indicator, Force indicator – Rockwell Automation 1756-L6x_L7x ControlLogix System User Manual User Manual

Page 195: Sd indicator, Run indicator force indicator sd indicator

Advertising
background image

Rockwell Automation Publication 1756-UM001O-EN-P - October 2014

195

Troubleshoot the Module

Appendix A

1756-L7x Controller
Status Indicators

The status indicators are below the status display on the controller. They indicate
the state of the controller as described in these tables.

RUN Indicator

Use the mode switch on the front of the controller or use the Controller Status
menu in the Logix Designer application to change the controller mode that is
shown by the RUN indicator.

FORCE Indicator

The Force indicator shows if I/O forces are enabled on the controller.

SD Indicator

The SD indicator shows if the SD card is in use.

Table 52 - RUN Indicator

State

Description

Off

The controller is in Program or Test mode.

Steady green

The controller is in Run mode.

Table 53 - FORCE Indicator

State

Description

Off

No tags contain I/O force values.

Solid amber

I/O forces are active (enabled) though I/O force values and can be configured.
Use caution if you install (add) a force. If you install (add) a force, it immediately takes
effect.

Flashing amber

One or more input or output addresses have been forced to an On or Off state, but the forces have
not been enabled.
Use caution if you enable I/O forces. If you enable I/O forces, all existing I/O forces also
take effect.

Table 54 - SD Indicator

State

Description

Off

No activity is occurring with the SD card.

Flashing green

The controller is reading from or writing to the SD card.
Do not remove the SD card while the controller is reading or writing.

Solid green

Flashing red

The SD card does not have a valid file system.

Solid red

The controller does not recognize the SD card.

Advertising