If the auto configuration is not successful, verify that the correct Comm
Port was selected.

7.

Click Close.

Upgrade Controller Firmware

You can choose to upgrade controller firmware by using one of these tools:

ControlFLASH™ software that is packaged with the Studio 5000
environment

AutoFlash feature of the Logix Designer application

To upgrade your controller firmware, complete the tasks that are listed in this
table.

Determine Required Controller Firmware

Use

Table 4

to determine what firmware revision is required for your controller.

Task

Page

Determine Required Controller Firmware

52

Obtain Controller Firmware

53

Use ControlFLASH Software to Upgrade Firmware

53

Use AutoFlash to Upgrade Firmware

56

IMPORTANT

The controller must be in Remote Program or Program mode and all major
recoverable faults must be cleared to accept upgrades.

Table 4 - Firmware Required for Controllers

Controller

Series

Use this firmware revision

1756-L61

A

12.x or later

B

13.40 or later

1756-L62

A

12.x or later

B

13.40 or later

1756-L63 A

If not using a CompactFlash card, 10.x or later
If using a CompactFlash card, 11.x or later

B

13.40 or later

1756-L63XT

B

13.40 or later

1756-L64

B

16 or later

1756-L65

B

17 or later

1756-L71

A

20 or later

1756-L72

A

19 or later

1756-L73

A

19 or later

1756-L73XT

A

19 or later

1756-L74

A

19 or later