88

Rockwell Automation Publication 1756-UM001O-EN-P - October 2014

Chapter 5

Communication Networks

Software for EtherNet/IP Networks

Table 14

lists software that is used with the EtherNet/IP networks and modules

.

Connections Over an EtherNet/IP Network

You indirectly determine the number of connections the controller uses by
configuring the controller to communicate with other devices in the system.
Connections are allocations of resources that provide more reliable
communication between devices as compared to unconnected messages.

All EtherNet/IP connections are unscheduled. The requested packet interval
(RPI) for I/O control or the program, such as a MSG instruction triggers an
unscheduled connection. Unscheduled messaging lets you send and receive data
when needed.

Double Data Rate (DDR) Backplane Communication

DDR communication can be achieved with the 1756-L7

x controller. The

following communication modules support DDR when used with the 1756-L7

x

controller. Minimum series are indicated as follows:

1756-EN2T/C

1756-EN2TR/B

1756-EN2TF/B

1756-EN2TXT/C

1756-EN3TR/A

1756-RM/B

DDR communication is achieved most efficiently when all modules in the
communication path are DDR modules, or, in other words, as one conversation
(connection) only between DDR modules.

DDR communication is achievable in a chassis with a mix of DDR and non-
DDR modules. The DDR communication occurs between the modules that

Table 14 - Software for Use with EtherNet/IP Networks

Software

Is used to

Required or Optional

Logix Designer application

Configure ControlLogix projects.
Define EtherNet/IP communication.

Required

RSLinx Classic or RSLinx®
Enterprise

Configure communication devices.
Provide diagnostics.
Establish communication between devices.

Required

BOOTP/DHCP Utility

Assign IP addresses to devices on an EtherNet/IP network.

Optional

RSNetWorx™ for EtherNet/IP

Configure EtherNet/IP devices by IP addresses and/or

host names.

Provide bandwidth status.