94

Rockwell Automation Publication 1756-UM001O-EN-P - October 2014

Chapter 5

Communication Networks

ControlLogix DeviceNet Bridge Module and Linking Devices

Table 18

lists the available ControlLogix DeviceNet bridge and linking devices

that can be used with the DeviceNet network.

Software for DeviceNet Networks

Table 19

lists software that is used with the DeviceNet networks and modules.

Connections Over DeviceNet Networks

The ControlLogix controller requires two connections for each 1756-DNB
module. One connection is for module status and configuration. The other
connection is a rack-optimized connection for the device data.

ControlLogix DeviceNet Module Memory

The 1756-DNB module has fixed sections of memory for the input and output
data of the DeviceNet devices on the network. Each device on your network
requires some input or output memory of the scanner. Some devices send and
receive data, so they need input and output memory. The 1756-DNB module
supports up to add the following:

124 DINTs of input data

123 DINTs of output data

Table 18 - DeviceNet Communication Modules and Capabilities

Module/Device

Is used to

1756-DNB

Control I/O modules.
Communicate with other DeviceNet devices (via messages).

1788-EN2DNR

Link an EtherNet/IP network to a DeviceNet network.

1788-CN2DN

Link a ControlNet network to a DeviceNet network.

Table 19 - Software for Use with DeviceNet Networks

Software

Is used to

Required or Optional

Logix Designer application

Configure ControlLogix projects.
Define DeviceNet communication.

Required

RSNetWorx™ for DeviceNet™

Configure DeviceNet devices.
Define the scan list for those devices.

RSLinx Classic or Enterprise

Configure communication devices.
Provide diagnostics.
Establish communication between devices.