Estimate 1756-ba2 battery life – Rockwell Automation 1756-L6x_L7x ControlLogix System User Manual User Manual

Page 75

Advertising
background image

Rockwell Automation Publication 1756-UM001O-EN-P - October 2014

75

Start Using the Controller

Chapter 3

Estimate 1756-BA2 Battery Life

The 1756-BA2 batteries are for use in 1756-L6

x/B controllers. Use

Table 9

to

estimate how much time can elapse before the battery becomes low.

Table 9 - Worst-case Estimates of 1756-BA2 Life according to Temperatures and Power Cycles

Temperature 2.54 cm (1 in.) Below
the Chassis, max

Power Cycles

Battery Life Before the BAT Status Indicator Turns Red

Project Size

1 MB

2 MB

4 MB

8 MB

16 MB

-25…35 °C (-13…95 °F)

3 per day

3 years

3 years

26 months

20 months

10 months

2 per day or less

3 years

3 years

3 years

31 months

16 months

41…45 °C (105.8…113 °F)

3 per day

2 years

2 years

2 years

20 months

10 months

2 per day or less

2 years

2 years

2 years

2 years

16 months

46…50 °C (105.8…113 °F)

3 per day or less

16 months

16 months

16 months

16 months

10 months

51…55 °C (123.8…131 °F)

3 per day or less

11 months

11 months

11 months

11 months

10 months

56…70 °C (132.8…158 °F)

3 per day or less

8 months

8 months

8 months

8 months

8 months

Advertising