A common application layer with ControlNet and DeviceNet networks

Network connections via an RJ45 cable

Support half/full duplex 10 MB or 100 MB operation

Support standard switches

ControlLogix EtherNet/IP Communication Modules

For EtherNet/IP network communication in a ControlLogix system, you have
several modules to choose from.

Table 13

lists modules and their primary

features.

Table 13 - EtherNet/IP Communication Modules and Capabilities

Module

Is used to

1756-ENBT

Connect controllers to I/O modules (requires an adapter for distributed I/O).
Communicate with other EtherNet/IP devices (messages).
Serve as a pathway to share data between Logix5000 controllers (produce/consume).
Bridge EtherNet/IP nodes to route messages to devices on other networks.

1756-EN2T

Perform the same functions as a 1756-ENBT module, with twice the capacity for more

demanding applications.

Provide a temporary configuration connection via the USB port.
Configure IP addresses quickly by using rotary switches.

1756-EN2F

Perform the same functions as a 1756-EN2T module.
Connect fiber media by an LC fiber connector on the module.

1756-EN2TR

Perform the same functions as a 1756-EN2T module.
Support communication on a ring topology for a Device Level Ring (DLR) single-fault

tolerant ring network.

1756-EN2TRXT

Perform the same functions as a 1756-EN2T module.
Support communication on a ring topology for a Device Level Ring (DLR) single-fault

tolerant ring network.

Operate in extreme environments with -25…70 °C (-13…158 °F) temperatures.

1756-EN3TR

Perform the same functions as the 1756-EN2TR module.
Extended Integrated Motion on EtherNet/IP network.
Support of up to 128 motion axes.

1756-EN2TSC

Perform the same functions as a 1756-ENBT module, with twice the capacity for more

demanding applications.

Provide a temporary configuration connection via the USB port.
Configure IP addresses quickly by using rotary switches.

1756-EN2TXT

Perform the same functions as a 1756-EN2T module.
Operate in extreme environments with -25…70 °C (-13…158 °F) temperatures.

1756-EWEB

Provide customizable web pages for external access to controller information.
Provide remote access via an internet browser to tags in a local ControlLogix controller.
Communicate with other EtherNet/IP devices (messages).
Bridge EtherNet/IP nodes to route messages to devices on other networks.
Support Ethernet devices that are not EtherNet/IP-based with a socket interface.
This module does not provide support for I/O or produced/consumed tags.