Factors – BECKHOFF EL7037 User Manual

Page 115

Advertising
background image

Commissioning

Fig. 125: Position lag monitoring parameters

K

v

factors

In the NC two proportional factors K

v

can be set under "Axis 1_Ctrl " in tab "Parameter". First select the

position controller Type with two P constants (with K

a

) under the “NC Controller” tab. The two P constants

are for the Standstill range and for the Moving range (see Fig. "Setting the proportional factor K

v

"). The

factors can be used to set the start-up torque and the braking torque to a different value than the drive
torque. The threshold value can be set directly below (Position control: Velocity threshold V dyn) between
0.0 (0%) and 1.0 (100%). Fig. "Velocity ramp with K factor limit values" shows speed ramp with thresholds of
30%. The K

v

factor for Standstill (t

1

and t

3

) can be different than the Kv factor for Moving (t

2

). In this case the

same factor was used, since for stepper motors this function is less crucial than for DC motors.

Fig. 126: Speed ramp with K factor limit values

EL70x7

115

Version 1.0

Advertising
This manual is related to the following products: