1 el7037, Object description and parameterization – BECKHOFF EL7037 User Manual

Page 155

Advertising
background image

Configuration by means of the TwinCAT System Manager

6

Configuration by means of the TwinCAT System
Manager

6.1

EL7037

6.1.1

Object description and parameterization - Profile-specific
objects

Note

EtherCAT XML Device Description

The display matches that of the CoE objects from the EtherCAT XML Device Description.
We recommend downloading the latest XML file from the download area of the Beckhoff
website
and installing it according to installation instructions.

Note

Parameterization via the CoE list (CAN over EtherCAT)

The terminal is parameterized via the CoE - Online tab (double-click on the respective ob-
ject) or via the Process Data tab (allocation of PDOs). Please note the following general
CoE information [

}

 32] when using/manipulating the CoE parameters:

- Keep a startup list if components have to be replaced
- Differentiation between online/offline dictionary, existence of current XML description
- use "CoE reload" for resetting changes

Attention

Risk of damage to the device!

We strongly advise not to change settings in the CoE objects while the axis is active, since
this could impair the control.

Introduction

The CoE overview contains objects for different intended applications:

Object overview

• Restore object [

}

 155]

• Configuration data [

}

 156]

• Command object [

}

 160]

• Input data [

}

 161]

• Output data [

}

 162]

• Information / diagnostic data (channel specific) [

}

 163]

• Manufacturer configuration data (device-specific) [

}

 165]

• Information / diagnostic data (device-specific) [

}

 165]

• Standard objects [

}

 166]

Restore object

Index 1011 Restore default parameters

Index

Name

Meaning

Data type

Flags

Default value

1011:0

Restore default
parameters

Restore default parameters

UINT8

RO

0x01 (1

dec

)

1011:01

SubIndex 001

If this object is set to "0x64616F6C" in the set value dia-
log, all backup objects are reset to their delivery state.

UINT32

RW

0x00000000 (0

dec

)