Index a010 stm diag data ch.1 – BECKHOFF EL7037 User Manual

Page 188

Advertising
background image

Configuration by means of the TwinCAT System Manager

Index 9020 POS Info data Ch.1

Index

Name

Meaning

Data type

Flags

Default value

9020:0

POS Info data
Ch.1

Maximum subindex

UINT8

RO

0x04 (4

dec

)

9020:01

Status word

Status word

UINT16

RO

0x0000 (0

dec

)

9020:03

State (drive con-
troller)

permitted values:

UINT16

RO

0x0000 (0

dec

)

0: Init

1: Idle

272: Go cam

273: On cam

16: Start

17: Acceleration

18: Constant

19: Deceleration

288: Go sync impulse

289: Leave cam

4096: Pre target

4097: In target

32: Emergency Stop

33: Normal stop

304: Calibration stop

8192: Drive end

8193: Wait for init

320: Is calibrated

321: Not calibrated

16384: Drive warning

32768: Error

65535: Undefined

256: Calibration start

9020:04

Actual position lag Current step error

INT32

RO

0x00000000 (0

dec

)

Index A010 STM Diag data Ch.1

Index

Name

Meaning

Data type

Flags

Default value

A010:0

STM Diag data
Ch.1

Maximum subindex

UINT8

RO

0x11 (17

dec

)

A010:01

Saturated

Driver stage operates with maximum duty cycle

BOOLEAN

RO

0x00 (0

dec

)

A010:02

Over temperature Internal terminal temperature is greater than 80 °C

BOOLEAN

RO

0x00 (0

dec

)

A010:03

Torque overload

Duty cycle output at 100%

BOOLEAN

RO

0x00 (0

dec

)

A010:04

Under voltage

Supply voltage less than 7 V

BOOLEAN

RO

0x00 (0

dec

)

A010:05

Over voltage

Supply voltage 10 % higher than the nominal voltage
(see 8010:03)

BOOLEAN

RO

0x00 (0

dec

)

A010:06

Short circuit

Short circuit of motor coil

BOOLEAN

RO

0x00 (0

dec

)

A010:08

No control power

No power supply to driver stage

BOOLEAN

RO

0x00 (0

dec

)

A010:09

Misc error

• Initialization failed or

• Internal terminal temperature is higher than 100

°C (see F80F:05)

BOOLEAN

RO

0x00 (0

dec

)

A010:0A

Configuration

CoE change has not yet been adopted into the current
configuration

BOOLEAN

RO

0x00 (0

dec

)

A010:0B

Motor stall

A loss of step has occurred

BOOLEAN

RO

0x00 (0

dec

)

A010:11

Actual operation
mode

permitted values:

BIT4

RO

0x00 (0

dec

)

0: Automatic

1: Velocity direct

2: Velocity controller

3: Position controller

4: Ext. Velocity mode

5: Ext. Position mode

6: Velocity sensorless

EL70x7

188

Version 1.0

Advertising