7 basic principles: "positioning interface, Basic principles: "positioning interface – BECKHOFF EL7037 User Manual

Page 140

Advertising
background image

Commissioning

Fig. 162: Entering the velocity

• The changeover to sensorless operation take place via a programmable, motor-dependent switching

speed. The switching speed is usually in the range between half and three revolutions per second
(crossover velocity 1, Index 8014:07 [

}

 182]). And subsequently a note with:

Note

Parameterization Sensorless operation

All parameters required for sensorless operation can be found in the table "Overview of pa-
rameter settings for individual operating modes [

}

 124]".

However, all the required necessary parameters are pre-specified via a startup list for the
respective motor types.

5.4.7

Basic principles: "Positioning interface"

The "Positioning interface" offers the user a possibility to implement travel commands directly on the
terminal.

Predefined PDO Assignment

The "Predefined PDO Assignment [

}

 103]" enables a simplified selection of the process data. Select the

function “Positioning interface” or “Positioning interface compact” in the lower part of the Process data tab.
As a result, all necessary PDOs are automatically activated and the unnecessary PDOs are deactivated.

Fig. 163: Predefined PDO Assignment

Parameter set

Two objects are at the user’s disposal in the CoE for the configuration – the “POS Settings” (Index 8020
[

}

 183]) and the “POS Features” (Index 8021 [

}

 184]).

EL70x7

140

Version 1.0

Advertising