186] is set in, 186] is set and a rising edge occurs at, 186] is set and a falling edge occurs – BECKHOFF EL7037 User Manual

Page 186: 186] is set in the, 186] is set and a rising edge occurs at the latch, 186] is set and a falling edge occurs at the latch, 0x7000:01, 186] - enable latch c, 0x7000:02, 186] - enable latch extern on

Advertising
background image

Configuration by means of the TwinCAT System Manager

Index 6020 POS Inputs Ch.1

Index

Name

Meaning

Data type

Flags

Default value

6020:0

POS Inputs Ch.1

Maximum subindex

UINT8

RO

0x16 (22

dec

)

6020:01

Busy

A current travel command is active

BOOLEAN

RO

0x00 (0

dec

)

6020:02

In-Target

Motor has arrived at target

BOOLEAN

RO

0x00 (0

dec

)

6020:03

Warning

A warning has occurred

BOOLEAN

RO

0x00 (0

dec

)

6020:04

Error

an error has occurred

BOOLEAN

RO

0x00 (0

dec

)

6020:05

Calibrated

Motor is calibrated

BOOLEAN

RO

0x00 (0

dec

)

6020:06

Accelerate

Motor is in the acceleration phase

BOOLEAN

RO

0x00 (0

dec

)

6020:07

Decelerate

Motor is in the deceleration phase

BOOLEAN

RO

0x00 (0

dec

)

6020:11

Actual position

Current target position of the travel command generator

UINT32

RO

0x00000000 (0

dec

)

6020:21

Actual velocity

Current set velocity of the travel command generator

INT16

RO

0x0000 (0

dec

)

6020:22

Actual drive time

Travel command time information (see subindex 8021:11
[

}

 184])

UINT32

RO

0x00000000 (0

dec

)

Output data

Index 7000 ENC Outputs Ch.1

Index

Name

Meaning

Data type

Flags

Default value

7000:0

ENC Outputs
Ch.1

Maximum subindex

UINT8

RO

0x11 (17

dec

)

7000:01

Enable latch C

Activate latching via the C-track.

BOOLEAN

RO

0x00 (0

dec

)

7000:02

Enable latch ex-
tern on positive
edge

Activate external latch with positive edge.

BOOLEAN

RO

0x00 (0

dec

)

7000:03

Set counter

Set the counter value.

BOOLEAN

RO

0x00 (0

dec

)

7000:04

Enable latch ex-
tern on negative
edge

Activate external latch with negative edge.

BOOLEAN

RO

0x00 (0

dec

)

7000:11

Set counter value This is the counter value to be set via "Set counter".

UINT32

RO

0x00000000 (0

dec

)

Index 7010 STM Outputs Ch.1

Index

Name

Meaning

Data type

Flags

Default value

7010:0

STM Outputs
Ch.1

Maximum subindex

UINT8

RO

0x21 (33

dec

)

7010:01

Enable

activates the output stage

BOOLEAN

RO

0x00 (0

dec

)

7010:02

Reset

all errors that may have occurred are reset by setting this
bit (rising edge)

BOOLEAN

RO

0x00 (0

dec

)

7010:03

Reduce torque

Reduced torque (coil current) is active (see subindex
8010:02 [

}

 180])

BOOLEAN

RO

0x00 (0

dec

)

7010:0C

Digital output 1

Digital output 1

BOOLEAN

RO

0x00 (0

dec

)

7010:11

Position

Set position specification
Unit: Increments [

}

 128]

UINT32

RO

0x00000000 (0

dec

)

7010:21

Velocity

Set velocity specification
Unit: +/- 32767 corresponds to +/- 100% [

}

 126]

INT16

RO

0x0000 (0

dec

)

Index 7020 POS Outputs Ch.1 (part 1)

Index

Name

Meaning

Data type

Flags

Default value

7020:0

POS Outputs
Ch.1

Maximum subindex

UINT8

RO

0x24 (36

dec

)

7020:01

Execute

Start travel command (rising edge), or prematurely abort
travel command (falling edge)

BOOLEAN

RO

0x00 (0

dec

)

7020:02

Emergency Stop

Prematurely abort travel command with an emergency
ramp (rising edge)

BOOLEAN

RO

0x00 (0

dec

)

7020:11

Target position

Specification of the target position

UINT32

RO

0x00000000 (0

dec

)

7020:21

Velocity

Specification of the maximum set velocity

INT16

RO

0x0000 (0

dec

)

EL70x7

186

Version 1.0

Advertising