Configuration by means of the TwinCAT System Manager

Index 1C32 SM output parameter (part 1)

Index

Name

Meaning

Data type

Flags

Default value

1C32:0

SM output param-
eter

Synchronization parameters for the outputs

UINT8

RO

0x20 (32

dec

)

1C32:01

Sync mode

Current synchronization mode:

• 0: Free Run

• 1: Synchronous with SM 2 event

• 2: DC-Mode - Synchronous with SYNC0 Event

• 3: DC-Mode - Synchronous with SYNC1 event

UINT16

RW

0x0001 (1

dec

)

1C32:02

Cycle time

Cycle time (in ns):

• Free Run: Cycle time of the local timer

• Synchronous with SM 2 event: Master cycle time

• DC-Mode: SYNC0/SYNC1 Cycle Time

UINT32

RW

0x000F4240
(1000000

dec

)

1C32:03

Shift time

Time between SYNC0 event and output of the outputs (in
ns, DC mode only)

UINT32

RO

0x00000000 (0

dec

)

1C32:04

Sync modes sup-
ported

Supported synchronization modes:

• Bit 0 = 1: free run is supported

• Bit 1 = 1: Synchronous with SM 2 event is

supported

• Bit 2-3 = 01: DC mode is supported

• Bit 4-5 = 10: Output shift with SYNC1 event (only

DC mode)

• Bit 14 = 1: dynamic times (measurement through

writing of 1C32:08 [

}

 176])

UINT16

RO

0x0C07 (3079

dec

)

1C32:05

Minimum cycle
time

Minimum cycle time (in ns)

UINT32

RO

0x0003D090
(250000

dec

)

1C32:06

Calc and copy
time

Minimum time between SYNC0 and SYNC1 event (in ns,
DC mode only)

UINT32

RO

0x00000000 (0

dec

)

1C32:07

Minimum delay
time

UINT32

RO

0x00000000 (0

dec

)

Index 1C32 SM output parameter (part2)

Index

Name

Meaning

Data type

Flags

Default value

1C32:08

Command

• 0: Measurement of the local cycle time is stopped

• 1: Measurement of the local cycle time is started

The entries 1C32:03 [

}

 176], 1C32:05 [

}

 176], 1C32:06

[

}

 176], 1C32:09 [

}

 176], 1C33:03 [

}

 177], 1C33:06

[

}

 176], and 1C33:09 [

}

 177] are updated with the maxi-

mum measured values.
For a subsequent measurement the measured values
are reset

UINT16

RW

0x0000 (0

dec

)

1C32:09

Maximum delay
time

Time between SYNC1 event and output of the outputs (in
ns, DC mode only)

UINT32

RO

0x00000000 (0

dec

)

1C32:0B

SM event missed
counter

Number of missed SM events in OPERATIONAL (DC
mode only)

UINT16

RO

0x0000 (0

dec

)

1C32:0C

Cycle exceeded
counter

Number of occasions the cycle time was exceeded in
OPERATIONAL (cycle was not completed in time or the
next cycle began too early)

UINT16

RO

0x0000 (0

dec

)

1C32:0D

Shift too short
counter

Number of occasions that the interval between SYNC0
and SYNC1 event was too short (DC mode only)

UINT16

RO

0x0000 (0

dec

)

1C32:14

Frame repeat time

UINT32

RW

0x00000000 (0

dec

)

1C32:20

Sync error

The synchronization was not correct in the last cycle,
(outputs were output too late; DC mode only)

BOOLEAN

RO

0x00 (0

dec

)

EL70x7

176

Version 1.0