Basics communication

Fig. 18: EtherCAT tab -> Advanced Settings -> Behavior -> Watchdog

Notes:

• the multiplier is valid for both watchdogs.

• each watchdog has its own timer setting, the outcome of this in summary with the multiplier is a

resulting time.

• Important: the multiplier/timer setting is only loaded into the slave at the start up, if the checkbox is

activated.
If the checkbox is not activated, nothing is downloaded and the ESC settings remain unchanged.

Multiplier

Multiplier

Both watchdogs receive their pulses from the local terminal cycle, divided by the watchdog multiplier:

1/25 MHz * (watchdog multiplier + 2) = 100 µs (for default setting of 2498 for the multiplier)

The standard setting of 1000 for the SM watchdog corresponds to a release time of 100 ms.

The value in multiplier + 2 corresponds to the number of basic 40 ns ticks representing a watchdog tick.
The multiplier can be modified in order to adjust the watchdog time over a larger range.

EL70x7

29

Version 1.0