Yaskawa P7B Drive Bypass User Manual

Page 101

Advertising
background image

Programming 5 - 7

"

Options - S "Speed Pot."; Bypass with speed potentiometer for speed control:

Hand mode speed command from speed potentiometer.
Auto mode speed command input signal, 0-10 VDC applied to Drive terminal A2.
Auto mode run/stop contact closure for Drive and Bypass applied to terminals TB1-3 and TB1-4.

"

Options - G, H, L, Q, or V "Serial Communications"; Bypass with serial communication for

control:

Hand mode speed command from Keypad/Operator.
Auto mode speed command input signal from serial communication.
Auto mode run/stop command for Drive from serial communication.
Auto mode run/stop contact closure for Bypass applied to terminals TB1-3 and TB1-4.

"

Options - G, H, L, Q, or V "Serial Communications"; Bypass with serial communication for

run/stop control and speed monitoring:

Hand mode speed command from Keypad/Operator.
Auto mode speed command input signal, 0-10 VDC applied to Drive terminal A2.
Auto mode run/stop command for Drive from serial communication.
Auto mode run/stop contact closure for Bypass applied to terminals TB1-3 and TB1-4.

Significant

Parameter Setting

Result

b1-01 = 1: Terminals (default)

Speed command source = Terminals

H3-13 = 1: Main Fref TA2

Main speed command source = Terminal A2 and the Aux speed command
source = Terminal A1

H3-08 = 0: 0-10 VDC

Terminal A2 is programmed for 0-10 VDC (Note –
Control PCB DIP switch S1-2 must also be OFF)

H3-09 = 2: Aux Reference (default)

Aux Terminal (A1) function is set to be a speed command input.

H1-03 = 3: Multi-Step Ref 1 (default) A terminal S5 input contact closure selects Aux Terminal (A1) as a preset

speed. This input contact is closed when H/O/A = Hand.

Significant

Parameter Setting

Result

b1-01 = 0: Operator

Speed command source = Keypad/Operator (d1-01)

H1-03 = 6C: Com/Inv Sel 2

A terminal S5 input contact closure allows b1-01 to select d1-01 (keypad) as a
preset speed. An open contact selects serial com for speed command and run/
stop. This input contact is closed when H/O/A = Hand.

Significant

Parameter Setting

Result

b1-01 = 0: Operator

Speed command source = Keypad/Operator (d1-01)

H3-08 = 0: 0-10 VDC

Terminal A2 is programmed for 0-10 VDC (Note – Control PCB DIP switch
S1-2 must also be OFF)

H3-09 = 2: Aux Reference (default)

Terminal A2 function is set to be a speed command input. This setting also
gives terminal A2 priority over d1-02 for “preset speed 2”, see Programming
Manual.

H1-02 = 3: Multi-Step Ref 1
S4 must be jumpered to SN

A terminal S4 input contact closure selects A2 as “preset speed 2” speed input.
The S4 input is jumpered to SN, therefore it is always closed.

H1-03 = 6C: Com/Inv Sel 2

A terminal S5 input contact closure allows b1-01 to select d1-01 (keypad) as a
preset speed. An open contact selects serial com for the run/stop command
(the serial com speed command is overridden by the preset speed above). This
input contact is closed when H/O/A = Hand.

H1-04 = 4: Multi-Step Ref 2 (default)
S6 must be jumpered to S5

A terminal S6 input contact closure selects d1-04 (keypad) as a speed input.
When open, the speed command is determined by “preset speed 2”. This input
contact is closed when H/O/A = Hand.

Advertising