Programming 5 - 13

When the output frequency has dropped below the DC Injection Start Frequency in b2-01 (Default = 0.5HZ) DC current will
be injected in the motor at a level determined by b2-02 (50% Default). The DC Injection condition will occur for the time
specified by b2-04 (0.0 Default), to establish the end point of the ramp. DC injection can be used to insure the motor is at zero
rpm prior to the Drive shutting off.

Fig 5.2 Deceleration to Stop

The actual deceleration time can be determined by the following formula

If S-Curve characteristics are specified by the Drive programming, they will add to the total time to stop.

1:Coast to stop: When the Run command is removed, the Drive will turn off its output and the motor will coast (uncon-

trolled deceleration). The friction of the driven equipment will eventually overcome any residual inertia of
the system and the rotation will stop.

Fig 5.3 Coast to Stop

IMPORTANT

After a stop is initiated, a subsequent Run commands input before the Minimum Baseblock Time (L2-03)
has expired, will be ignored.

ON

OFF

Run Command

Output Frequency

Deceleration Time (C1-02)

DC Injection Brake

100 %

0 %

TIME

| b2-04 |

b2-01

(CLOSED)

(OPEN)

02)

-

(C1

Time

Decel

active

of

Setting

04)

-

(E1

Frequency

Maximum

command

stop

of

at time

Freq.

Output

Stop

to

Time

×

=

02 or C1-04)

ON

OFF

Run Command

Output Frequency

Drive Output Frequency Interrupted

100 %

0 %

TIME

Motor Speed

(CLOSED)

(OPEN)

Advertising