Capacity Related Parameters B - 4

The following tables detail the factory default settings for the parameters that are affected by the setting of parameter o2-04.

Table B.3 208/240VAC Drives

Drive Model

CIMR-_ _ _

Nominal

Hp

Factory

Default

for

b8-04

Factory

Default

for

C6-02

Factory

Default

for

E2-01

Factory

Default

for

E2-03

Factory

Default

for

E2-05

Factory

Default

for

L2-02

Factory

Default

for

L2-03

Factory

Default

for

L2-04

Factory

Default

for

L8-02

Factory

Default

for

L8-06

P7U20P4

0.5/0.75

288.2

10kHz

1.9

1.2

9.842

0.1

0.1

0.3

95

°

C

5

P7U20P7

2

223.7

10kHz

3.3

1.8

5.156

0.1

0.2

0.3

95

°

C

7.5

P7U21P5

1.5/2

169.4

10kHz

6.2

2.8

1.997

0.2

0.3

0.3

95

°

C

10

P7U22P2

3

156.8

8kHz

8.5

3.0

1.601

0.3

0.4

0.3

100

°

C

12

P7U23P7

5

122.9

10kHz

14.0

4.5

0.771

0.5

0.5

0.3

95

°

C

12

P7U25P5

7.5

94.75

15kHz

19.6

5.1

0.399

1.0

0.6

0.3

95

°

C

10

P7U27P5

10

72.69

15kHz

26.6

8.0

0.288

1.0

0.7

0.3

95

°

C

17

P7U2011

15

70.44

8kHz

39.7

11.2

0.230

1.0

0.8

0.3

95

°

C

21

P7U2015

20

63.13

10kHz

53.0

15.2

0.138

2.0

0.9

0.3

90

°

C

17

P7U2018

25

57.87

10kHz

65.8

15.7

0.101

2.0

1.0

0.6

100

°

C

15

P7U2022

30

51.79

10kHz

77.2

18.5

0.079

2.0

1.0

0.6

90

°

C

24

P7U2030

40

46.27

10kHz

105.0

21.9

0.064

2.0

1.1

0.6

90

°

C

20

P7U2037

50

38.16

5kHz

131.0

38.2

0.039

2.0

1.1

0.6

95

°

C

18

P7U2045

60

35.78

5kHz

160.0

44.0

0.030

2.0

1.2

0.6

100

°

C

20

P7U2055

75

31.35

8kHz

190.0

45.6

0.022

2.0

1.2

0.1

105

°

C

17

P7U2075

75/100

23.10

2kHz

260.0

72.0

0.023

2.0

1.3

0.1

110

°

C

16

P7U2090

125

20.65

2kHz

260.0

72.0

0.023

2.0

1.5

0.1

100

°

C

18

P7U2110

150

18.12

2kHz

260.0

72.0

0.023

2.0

1.7

0.1

95

°

C

20

Note: b8-04 = Energy Savings Coefficiant

C6-02 = Carrier Frequency

E2-01 = Motor Rated Current

E2-03 = Motor No-Load Current

E2-05 = Motor Line-to-Line Resistance

L2-02 = Momentary Power Loss Ride-Thru Time

L2-03 = Momentary Power Loss Minimun Base Block Time

L2-04 = Momentary Power Loss Voltage Recovery Ramp Time

L8-02 = Overheat Pre-Alarm Level

L8-06 = Input Phase Loss Detection Level