Parameters a - 8, Torque comp, Carrier freq – Yaskawa P7B Drive Bypass User Manual

Page 226: Preset reference, Table 1: parameter list (continued)

Advertising
background image

Parameters A - 8

Torque Comp

C4-01

!

Torque Compensation Gain
Torq Comp Gain

This parameter helps to produce better starting torque. It
determines the amount of torque or voltage boost based upon
motor current and motor resistance.

0.00 to 2.50

1.00

Programming

C4-02

Torque Compensation
Primary Delay Time
Torq Comp Time

This parameter adjusts a filter on the output of the torque
compensation function. Increase to add torque stability, decrease to
improve torque response.

0 to 10000

200ms

Programming

Carrier Freq

C6-02

Carrier Frequency Selection
CarrierFreq Sel

Carrier frequency sets the number of pulses per second of the out-
put voltage waveform.
0: Low Noise (Carrier frequency is randomly moduled for lower
audible noise)
1: Fc = 2.0 kHz
2: Fc = 5.0 kHz
3: Fc = 8.0 kHz
4: Fc = 10.0 kHz
5: Fc = 12.5 kHz
6: Fc = 15.0 kHz
F: Program (Determined by the settings of C6-03 thru C6-05)

0 to F

kVA

Dependent

Programming

C6-03

Carrier Frequency Upper
Limit
CarrierFreq Max

Maximum carrier frequency allowed when C6-02 = F.

0.4 to 15.0

kHz

kVA

Dependent

Programming

C6-04

Carrier Frequency Lower
Limit
CarrierFreq Min

Minimum carrier frequency allowed when C6-02 = F.

0.4 to 15.0

kHz

kVA

Dependent

Programming

C6-05

Carrier Frequency Propor-
tional Gain
CarrierFreq Gain

Sets the relationship of output frequency to carrier frequency when
C6-02 = F.

0 to 99

0

Programming

Preset Reference

d1-01

!

Frequency Reference 1
Reference 1

Digital preset speed command 1. Used when b1-01 = 0 and when
in "hand" mode. Setting units are affected by o1-03.

0.00 to

E1-04

Value

0.00Hz

Programming

d1-02

!

Frequency Reference 2
Reference 2

Digital preset speed command 2. Selected via multi-function input
terminals. Setting units are affected by o1-03.

0.00Hz

Programming

d1-03

!

Frequency Reference 3
Reference 3

Digital preset speed command 3. Selected via multi-function input
terminals. Setting units are affected by o1-03.

0.00Hz

Programming

d1-04

!

Frequency Reference 4
Reference 4

Digital preset speed command 4. Selected via multi-function input
terminals. Setting units are affected by o1-03.

0.00Hz

Programming

d1-17

!

Jog Frequency Reference
Jog Reference

Speed command used when a jog is selected via multi-function
input terminals. Setting units are affected by o1-03.

0.00 to

E1-04

Value

6.00Hz

Programming

!Denotes that parameter can be changed when the Drive is running.

Table 1: Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location