480 vac, Specifications c - 3 – Yaskawa P7B Drive Bypass User Manual

Page 257

Advertising
background image

Specifications C - 3

!

480 VAC

Table C.3 480VAC Drive and Bypass Specifications

Bypass Model Number P7B_ *

B001

B002

B003

B004

B007

B011

B014

B021/B027

B034

B040

Motor HP (460V)

0.5/0.75

1

1.5/2

3

5

7.5

10

15/20

25

30

Bypass rated output current (A)

1.6

2.1

3.4

4.8

7.6

11

14

21/27

34

40

Drive Model Number CIMR-P7U

40P4

40P7

41P5

42P2

43P7

45P5

47P5

4011

4015

4018

Drive rated output capacity (kVA)

1.4

1.6

2.8

4.0

5.8

9.5

13.0

21.0

26.0

30.0

Drive rated output current (A)

1.8

2.1

3.7

5.3

7.6

12.5

17.0

27.0

34.0

40.0

Drive max. output voltage (V)

3-phase; 380, 400, 415, 440, 460, or 480VAC (Proportional to input voltage.)

Drive max. output frequency (Hz)

120 Hz

Rated voltage (V)
Rated frequency (Hz)

3-phase, 380, 400, 415, 440, 460 or 480VAC, 50/60 Hz

Rated input current (A)

2.2

2.5

4.4

6.4

9.0

15

20

33

40

48

Allowable voltage fluctuation

+ 10%, - 15%

Allowable frequency fluctuation

±5%

Measures for
power supply
harmonics

DC Reactor

Optional

12-pulse
Rectification

Not possible

Table C.3 480VAC Drive Specifications (Continued)

Bypass Model Number P7B_ *

B052/B065

B077

B096

B124

B156

B180

B240

B302

Motor HP (460V)

40/50

60

75

100

125

150

200

250

300/350

400/450

500+

Bypass rated output current (A)

52/65

77

96

124

156

180

240

302

Drive Model Number CIMR-P7U

4030

4037

4045

4055

4075

4090

4110

4160

4185

4220

4300

Drive rated output capacity (kVA)

51.0

59.0

73.0

95.0

120.0

140.0

180.0

230.0

315.0

390.0

510.0

Drive rated output current (A)

67.2

77.0

96.0

125.0

156.0

180.0

240.0

304.0

414.0

515.0

675.0

Drive max. output voltage (V)

3-phase, 380, 400, 415, 440, 460 or 480VAC (Proportional to input voltage)

Drive max. output frequency (Hz)

120 Hz

Max. voltage (V)
Rated frequency (Hz)

3-phase, 380, 400, 415, 440, 460, or 480VAC, 50/60 Hz

Rated input current (A)

74

85

106

134

172

198

264

334

456

567

743

Allowable voltage fluctuation

+ 10%, - 15%

Allowable frequency fluctuation

±5%

Measures for
power supply
harmonics

DC Reactor

Built-in

12-Pulse
Rectification

Possible

Note: The maximum applicable motor output is given for a standard 4-pole motor. When selecting the actual motor and Drive, be sure that the Bypass and

Drive's rated output current is equal to, or greater than, the motor's rated current.

A 3-wire phase-shifting transformer is required on the power supply for 12-pulse rectification.