Bypass control circuit terminal functions, Electrical installation 2 - 15 – Yaskawa P7B Drive Bypass User Manual

Page 53

Advertising
background image

Electrical Installation 2 - 15

!

Bypass Control Circuit Terminal Functions

The functions of the control circuit terminals are shown in Table 2.6.

Table 2.6 Bypass Control Circuit Terminals

Type

No.

Signal Name

Function

Signal Level

Digital

input

signals

TB1-3

Auto Mode run/stop command

Run when CLOSED; stopped when OPEN.

Dry

Contacts

TB1-4

TB1-1

NC Safety Circuit

Fault when OPEN

TB1-2

TB1-5

Customer Supplied Interlock

Enable Drive when Closed

TB1-6

TB1-17

Smoke Purge

*Transfer to Bypass when Closed

TB1-18

TB1-23

2 Motor “OR”

*Transfer to Motor 2 When Closed

TB1-24

TB1-25

Remote Transfer

*Transfer to Bypass when Closed

TB1-26

Analog

input

signals

(Drive)

+V

+15 VDC power output

+15 VDC power supply for analog Transmitters

+15 VDC

(Max. current: 20 mA)

A1

Analog Input or Speed Command

0 to +10 VDC/100%

0 to +10 V(20 k

)

A2

Multi-function analog input

4 to 20 mA/100%

0 to +10 VDC/100% (H3-08)

Function set by

H3-09.

4 to 20 mA(250

)

0 to +10 V(20k

)

AC

Analog input common

E(G)

Shield wire, optional ground line

connection point

Digital

output

signals

TB1-7

Running on Drive

CLOSED During Operation

Dry contacts

Contact capacity:

1 A max. at 250 VAC

1 A max. at 30 VDC

TB1-8

TB1-9

Running on Bypass

TB1-10

TB1-11

Drive Fault

11/12 CLOSED During Fault Condition

12/13 OPEN During Fault Condition

TB1-12

TB1-13

TB1-14

Motor Overload or

Safety Circuit Fault

14/15 CLOSED During Fault Condition

15/16 OPEN During Fault Condition

TB1-15

TB1-16

Analog

output

signals

(Drive)

FM

Multi-function analog output

Frequency Output

0 to +10 VDC/100% frequency

Multi-function

analog monitor 1

Function set by

H4-01

0 to +10 VDC max. ±5%

2 mA max.

AC

Analog output common

AM

Multi-function analog output

Current Monitor

0 to +10 VAC/100%
Drive's rated current

Multi-function

analog monitor 2

Function set by

H4-04

* Switch Selectable Options