Parameters a - 6, Table 1: parameter list (continued) – Yaskawa P7B Drive Bypass User Manual

Page 224

Advertising
background image

Parameters A - 6

b5-10

PI Output Gain Setting
Output Gain

Sets the output gain of the PI controller.

0.0 to 25.0

1.0

Quick Setting

b5-11

PI Output Reverse Selection
Output Rev Sel

0: 0 limit (when PI output goes negative Drive stops)
1: Reverse (when PI goes negative Drive reverses)
0 limit automatic when reverse prohibit is selected using b1-04

0 or 1

0

Quick Setting

b5-12

PI Feedback Reference
Missing Detection Selection
Fb los Det Sel

0: Disabled
1: Alarm
2: Fault

0 to 2

0

Quick Setting

b5-13

PI Feedback Loss Detection
Level
Fb los Det Lvl

Sets the PI feedback loss detection level as a percentage of
maximum frequency (E1-04).

0 to 100

0%

Quick Setting

b5-14

PI Feedback Loss Detection
Time
Fb los Det Time

Sets the PI feedback loss detection delay time in terms of seconds.

0.0 to 25.5

1.0sec

Quick Setting

b5-15

Sleep Function Start
Level
Sleep Level

Sets the sleep function start frequency.

0.0 to 200.0

0.0Hz

Quick Setting

b5-16

Sleep Delay Time
Sleep Time

Sets the sleep function delay time in terms of seconds.

0.0 to 25.5

0.0sec

Quick Setting

b5-17

PI Accel/Decel Time
PI Acc/Dec Time

Applies an accel/decel time to the PI setpoint reference.

0.0 to 25.5

0.0sec

Quick Setting

b5-18

PI Setpoint Selection
PI Setpoint Sel

0: Disabled
1: Enabled

0 or 1

0

Quick Setting

b5-19

PI Setpoint Value
PI Setpoint

*Depends on b5-20.

0.00 to
100.00

0.00%

Quick Setting

b5-20

PI Setpoint Display Scaling
Setpoint Scaling

Set display/setting unit of b5-19.

0 to 39999

1

Quick Setting

b5-21

PI Sleep Input Source
PI Sleep Source

Input Source Selection for Sleep function Mode.
0: PI Input
1: PI Setpoint
2: Snooze

0 to 2

1

Quick Setting

b5-22

!

PI Snooze Level
Snooze Level

Sets the PI snooze function start level as a percentage of maximum
frequency (E1-04).

0 to 100

0%

Quick Setting

b5-23

PI Snooze Delay Time
Snooze Delay Time

Sets the PI snooze function delay time in terms of seconds.

0 to 3600

0sec

Quick Setting

b5-24

PI Snooze Deactivation Level
Wake-Up Level

When the PI feedback drops below this level, normal PI operation
starts again. Set as a percentage of maximum frequency (E1-04).

0 to 100

0%

Quick Setting

b5-25

PI Setpoint Boost Setting
Setpoint Boost

Temporary increase of PI setpoint to create an overshoot of the
intended PI setpoint.

0 to 100

0%

Quick Setting

b5-26

PI Maximum Boost Time
Max Boost Time

Sets a time limitation for reaching temporarily boosted PI setpoint
(intended PI setpoint + b5-25).

0 to 3600

0sec

Quick Setting

b5-27

PI Snooze Feedback Level
Snooze Feedback

PI snooze mode will be activated when PI feedback is above this
level. Set as a percentage of maximum frequency (E1-04).

0 to 100

60%

Quick Setting

b5-28

PI Feedback Square Root
Function Selection
PI Feedback SqRt

0: Disabled
1: Enabled

0 or 1

0

Quick Setting

b5-29

PI Square Root Gain
PI Fb SqRt Gain

A multiplier applied to the square root of the feedback.

0.00 to 2.00

1.00

Quick Setting

b5-30

Output Square Root
Monitor Selection
PI Out Moni SqRt

0: Disabled
1: Enabled

0 or 1

0

Quick Setting

!Denotes that parameter can be changed when the Drive is running.

Table 1: Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Menu

Location