Communications D - 9

Modbus Data Tables

The data tables are shown below. The types of data are as follows: Reference data, monitor data and broadcast data.

!

Reference Data

The reference data table is shown below. Reference data can be read and written to.

Table D.4 Reference Data

Register No.

Contents

0000H

Reserved

0001H

Frequency reference

Bit 0

Run/stop command

1: Run 0: Stop

Bit 1

Forward/reverse operation

1: Reverse 0: Forward

Bit 2

External fault

1: Fault (EFO)

Bit 3

Fault reset

1: Reset command

Bit 4

ComNet

Bit 5

ComCtrl

Bit 6

Multi-function digital input command 3

Bit 7

Multi-function digital input command 4

Bit 8

Multi-function digital input command 5

Bit 9

Multi-function digital input command 6

Bit A

Multi-function digital input command 7

Bits B to F Not used

0002H

Frequency reference (Set units using parameter o1-03)

0003H to 0005H

Not used

0006H

PI Setpoint

0007H

Analog output 1 setting (-11 V = 726 to 11 V = 726)

10V = 660

0008H

Analog output 2 setting (-11 V = 726 to 11 V = 726)

10V = 660

0009H

Multi-function contact output setting

Bit 0

Digital output 1 (Terminal M1-M2)

1: ON 0: OFF

Bit 1

Digital output 2 (Terminal M3-M4)

1: ON 0: OFF

Bit 2

Not Used

Bits 3 to 5

Not used

Bit 6

Set fault contact (terminal MA-MC) output using bit 7. 1: ON 0: OFF

Bit 7

Fault contact (terminal MA-MC)

1: ON 0: OFF

Bits 8 to F

Not used

000AH to 000EH Not used

000FH

Reference selection settings

Bit 0

Not used

Bit 1

Input PI setpoint 1: Enabled 0: Disabled

Bits 3 to B

Not used

C

Broadcast data terminal S5 input 1: Enabled 0: Disabled

D

Broadcast data terminal S6 input 1: Enabled 0: Disabled

E

Broadcast data terminal S7 input 1: Enabled 0: Disabled

F

Not used

Note: Write 0 to all unused bits. Also, do not write data to reserved registers.