Modbus data tables, Reference data, Communications d - 9 – Yaskawa P7B Drive Bypass User Manual
Page 267

Communications D - 9
Modbus Data Tables
The data tables are shown below. The types of data are as follows: Reference data, monitor data and broadcast data.
!
Reference Data
The reference data table is shown below. Reference data can be read and written to.
Table D.4 Reference Data
Register No.
Contents
0000H
Reserved
0001H
Frequency reference
Bit 0
Run/stop command
1: Run 0: Stop
Bit 1
Forward/reverse operation
1: Reverse 0: Forward
Bit 2
External fault
1: Fault (EFO)
Bit 3
Fault reset
1: Reset command
Bit 4
ComNet
Bit 5
ComCtrl
Bit 6
Multi-function digital input command 3
Bit 7
Multi-function digital input command 4
Bit 8
Multi-function digital input command 5
Bit 9
Multi-function digital input command 6
Bit A
Multi-function digital input command 7
Bits B to F Not used
0002H
Frequency reference (Set units using parameter o1-03)
0003H to 0005H
Not used
0006H
PI Setpoint
0007H
Analog output 1 setting (-11 V = 726 to 11 V = 726)
→
10V = 660
0008H
Analog output 2 setting (-11 V = 726 to 11 V = 726)
→
10V = 660
0009H
Multi-function contact output setting
Bit 0
Digital output 1 (Terminal M1-M2)
1: ON 0: OFF
Bit 1
Digital output 2 (Terminal M3-M4)
1: ON 0: OFF
Bit 2
Not Used
Bits 3 to 5
Not used
Bit 6
Set fault contact (terminal MA-MC) output using bit 7. 1: ON 0: OFF
Bit 7
Fault contact (terminal MA-MC)
1: ON 0: OFF
Bits 8 to F
Not used
000AH to 000EH Not used
000FH
Reference selection settings
Bit 0
Not used
Bit 1
Input PI setpoint 1: Enabled 0: Disabled
Bits 3 to B
Not used
C
Broadcast data terminal S5 input 1: Enabled 0: Disabled
D
Broadcast data terminal S6 input 1: Enabled 0: Disabled
E
Broadcast data terminal S7 input 1: Enabled 0: Disabled
F
Not used
Note: Write 0 to all unused bits. Also, do not write data to reserved registers.