Yaskawa P7B Drive Bypass User Manual

Page 134

Advertising
background image

Programming 5 - 40

As shown in Table 5.6, it is possible to use analog inputs in place of Frequency Reference 1 and Frequency

Reference 2.

#

If b1-01= “1: Terminals” then the analog input A1 will be used instead of Frequency Reference 1 for the first preset speed.
If b1-01= “0: Operator”, then Frequency Reference 1 will be used.

#

If H3-09= “2: Aux Reference” then the analog input A2 will be used instead of Frequency Reference 2 for the second

preset speed. If H3-09

2 then Frequency Reference 2 will be used.

IMPORTANT

The programming of d1-01 through d1-04 and d1-17 will be affected by the setting of o1-03. The programming
of these parameters will be in the units specified by Display Scaling parameter (o1-03).