D1 preset references, Programming 5 - 39, D1-17 jog frequency reference – Yaskawa P7B Drive Bypass User Manual

Page 133

Advertising
background image

Programming 5 - 39

!

d1 Preset References

"

d1-01 Frequency Reference 1

d1-02 Frequency Reference 2

d1-03 Frequency Reference 3

d1-04 Frequency Reference 4

Setting Range:

0.00 to E1-04 Value

Factory Default: d1-01 = 10.00 Hz

d1-02 = 6.00 Hz
d1-03 = 0.00 Hz
d1-04 = 40.00 Hz

d1-01, d1-02 and d1-04 are special parameter settings required by the Bypass logic circuit. See Table 5.1.

Fig 5.20 Preset Reference Timing Diagram example

"

d1-17 Jog Frequency Reference

Setting Range:

0.00 to E1-04 Value

Factory Default: 6.00 Hz

The Drive can be programmed to utilize digital inputs to change between four presets speeds and a jog speed. It is a two-step
process to set the Drive up for preset speeds. First, d1-01 through d1-04 and d1-17 must be programmed with the desired preset
speeds and the desired jog speed, respectively. Next, up to three of the Drive’s digital inputs (Terminals S3 through S7) need to be
programmed (via parameters H1-01 to H1-05) and wired (to normally open contacts) as Multi-step Speed Reference 1, Multi-step
Speed Reference 2, and Jog Frequency.

Table 5.7 Preset Speed Truth Table

Preset Speed

Terminal

programmed

as Multi-step

Reference 1

Terminal

programmed
as Multi-step

Reference 2

Terminal

programmed

as Jog

Reference

Details

1

OFF

OFF

OFF

Frequency Reference 1 (d1-01) or analog input A1

2

ON

OFF

OFF

Frequency Reference 2 (d1-02) or analog input A2

3

OFF

ON

OFF

Frequency Reference 3 (d1-03)

4

ON

ON

OFF

Frequency Reference 4 (d1-04)

5

-

-

ON*

Jog Frequency (d1-17)

*

The Jog Frequency input is given priority over the multi-step speeds.

RUN

Multi-step
Reference 1 Input

Multi-step
Reference 2 Input

Closed
Open

Closed
Open

Closed
Open

Closed
Open

Jog Input

Output

Speed

t

d1-01

d1-02

d1-03

d1-04

d1-17