Parameters A - 22

Hdwe Protection

L8-01

Internal Dynamic Braking Resis-
tor Protection Selection
DB Resistor Prot

0: Not Provided
1: Provided

0 or 1

0

Programming

L8-02

Overheat Pre-Alarm Level
OH Pre-Alarm Lvl

When the cooling fin temperature exceeds the value set
in this parameter, an overheat pre-alarm (OH) will
occur.

50 to 130

95°C

Programming

L8-03

Overheat Pre-Alarm Operation
Selection
OH Pre-Alarm Sel

Drive Operation upon OH Pre Alarm Detection.
0: Ramp to Stop (Decel Time C1-02).
1: Coast to Stop
2: Fast-Stop (Decel Time = C1-09).
3: Alarm Only

*0 to 2 is recognized as fault detection, and 3 is
recognized as alarm. (For the fault detection, the fault

contact operates.)

4: OH Alarm & Reduce (Continue operation and reduce

output frequency by L8-19)

0 to 4

4

Programming

L8-06

Input Phase Loss Detection Level
Ph Loss In Lvl

Monitors the DC Bus current ripple and activates when
one of the input phases is lost (PF).

0.0 to 25.0

5.0%

Programming

L8-09

Output Ground Fault Detection
Selection
Ground Fault Sel

Enables and disables Drive output ground fault
detection.
0: Disabled
1: Enabled

0 or 1

1

Programming

L8-10

Heatsink Cooling Fan Operation
Selection
Fan On/Off Sel

Controls the Heatsink Cooling Fan Operation.
0: Fan On-Run Mode (Fan will operate only when

Drive is running and for L8-11 seconds after RUN is
removed).

1: Fan Always On

(Cooling fan operates whenever

Drive is powered up.)

0 or 1

0

Programming

L8-11

Heatsink Cooling Fan Operation
Delay Time
Fan Delay Time

When L8-10=0 this parameter sets a delay time for
Cooling Fan de-energization after the run command is
removed.

0 to 300

300sec

Quick Setting

L8-12

Ambient Temperature Setting
Ambient Temp

When the Drive is installed in an ambient temperature
exceeding its rating, Drive overload (OL2) protection
level is reduced.

45 to 60°C

45°C

Programming

L8-15

OL2 Characteristic Selection at
Low Speeds
OL2 Sel @ L-Spd

This parameter assists in protecting the output transistor
junctions from overheating when output current is high
and output frequency is low.
0: Disabled
1: Enabled (L8-18 is active)

0 or 1

1

Programming

L8-18

Soft CLA Selection
Soft CLA Sel

Enables and disables current limit “A”
0: Disabled
1: Enabled.

0 or 1

1

Programming

L8-19

OH Frequency Reference
Reduction Level
Fref During OH

Sets the amount of frequency reference reduction when
an Overheat Pre-alarm (OH) is detected.

0.0

to

100.0

20.0%

Programming